Weishaupt WTC 60-A Operations Instructions Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 90
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
12
3
3.4 Prerequisites
Air inlets must be
kept clear!
Unimpeded combustion air
Included in delivery
The ready-to-use unit is delivered in a cardboard box.
The following parts are enclosed loose:
End user documents
•Wall bracket
Screw set with wall plugs
•Spacer
•Siphon with hose for condensate drainage
Application instructions
When transporting and storing the unit, the following
should be avoided:
•mechanical impact, such as: distortion,
warping, scratching
Contamination of any kind, e.g.: water, oils, greases,
solvents, dust, debris, aggressive steam, etc.
electrical impact, e.g.: through electrostatic discharge
or unnaturally large electric fields, see DIN EN 100
015 Part 1 and "Instruction for handling
electrostatically sensitive components" (techn.
information 821005 from Valvo)
climatic exposure, such as: temperatures outside of
the range -10°C...+60°C, condensation caused by
dew, rel. humidity above 75% as annual average.
Requirements relating to the installation location
The installation location, which should be frost free and
protected from humidity, must comply with local
regulation (combustion by-law, fire regulations).
Observe special regulations:
DVGW-TRGI (Germany)
•SVGW-Guidelines (Switzerland)
Requirements relating to combustion air
The combustion air must be free from aggressive
compounds (Halogene, Chloride, Fluoride, etc.) and from
contaminants (dust, building material, steam, etc.). The
unit should not be operated until all building work in the
installation location has been completed.
Flue gas duct
Important - Warranty for boiler replacement!
Supply air ducts, which have previously been used as a
chimney for solid fuel or oil firing plants, must only be
used as supply air duct once they have been thoroughly
cleaned. Thoroughly clean means that dust, sulphur, soot,
dirt and any diffused gases have been removed from the
duct material (e.g. paint, render, insulation). If unsure, the
internal sides of the duct should be sealed or concentric
flue gas pipes (accessory) should be used.
If the WTC is integrated into an existing heating system,
it must be ensured that rust, dirt and sludge have been
removed.
Non oxygen diffusion resistant plastic pipes must only be
connected via a separate heat exchanger, otherwise
deposits can cause damage and lead to operational
influences (localised overheating, noise or similar).
If necessary fit sludge strainer in the return
Flue gas connection to chimneys
Due to the water vapour content in flue gases with low
temperature and the additional condensation created in
the chimney, condensing boilers can only be connected
to moisture resistant house chimneys. The flue gas ducts
must comply with local authority regulations and country
specific requirements:
•(DE) DVGW (TRGI)
•(AT) ÖVGW
•(CH) SVGW, VKF Guidelines, Number 3.4.8
(Issue 1993)
Building regulation approved flue gas duct
The flue gas duct should have the same diameter as the
boiler flue gas socket.
Consultation with the appropriate district master
chimney sweep
Flue gas duct soundness test must be carried out