8.2 Sensor monitoring
8.3 Heating frost protection function
Boiler frost protection (without external sensor
QAC 31)
Tv < 8°C
Burner on with minimum load
•Pump on
Tv > 8°C + switch differential flow
temperature ( P32)
Burner off
Pump run on ( P41)
Frost protection also effective on output MFA,
if parametered as flow pump (P13).
System frost protection (with external sensor
QAC 31)
T
A act.
< T
system frost protection
( P23)
Pump starts every 5 hrs.,
Switch on duration = pump run on time (P41).
T
A act.
< T
system frost protection
– 5 K
Pump continuous run on
T
A act.
> T
system frost protection
Pump continuous run off
Frost protection is also effective on outputs MFA and
VA with function heating circuit pump (P13, P14).
With calorifier regulation P1/P2 the system frost
protection has no effect on the boiler circuit pump
(internal or connected to MFA/VA).
T
DHW
< 8°C
Frost protection heating on
T
DHW
> 8°C + switch differential DHW/2 ( P51)
Frost protection heating off
With frost protection heating the boiler temperature is
regulated to 8°C + DHW temperature increase ( P50),
the Tap symbol flashes.
Frost protection is also effective on outputs MFA
and VA with function DHW supply pump and
circulation pump.
8.4 DHW frost protection (version -W)
Display of sensor faults